#85860
avig
משתתף

בסד
ABB מובא בזו הלשון מקטלוג חברת

PR222DS/P – Tmax T4 and T5
Circuit breakers for power distribution
Electronic trip units

Neutral protection: available at 50%, 100% or 200% of the phase currents, or disabled,
it is applied to the overcurrent protections L, S and I.

For four-pole circuit breakers, protection of the neutral can be set to 50% or 100% of the phase
protection setting, by means of dip-switches on the front of the trip unit.
Setting the adjustment parameters of the protection functions is carried out directly from the front of the trip unit or remotely, thanks to the use of the PR212/D (IEC only) dialogue unit, available with Modbus or LON communication protocols.
ABB 2/

בברכה
avig
Smile